Indian Journal of Science and Technology
DOI: 10.17485/ijst/2016/v9i29/89083
Year: 2016, Volume: 9, Issue: 29, Pages: 1-4
Original Article
Sergey I. Khrenov, Daniil A. Matveev, Anna Y. Skorokhodova* and Anton V. Zhuykov
National Research University, [email protected]
[email protected]
[email protected]
[email protected]
*Author for correspondence
Anna Y. Skorokhodova
National Research University
Email:[email protected]
The paper presents the experimental results of performance evaluation of two types of Arc Suppression Reactors (ASRs): traditional (plunger-type) and Magnetically Controlled (MC-type). The aperiodic component in reactor current is observed and its influence on reactors response speed is analyzed. It is shown that the delay in complete capacitive earth-fault current compensation is determined mostly by aperiodic component and not by forcing of magnetic excitation of MC-type ASRs. From this point of view ASRs of both type show similar performance and the criterion for their correct comparison is still has to be discovered.
Keywords: Arc Suppression, Capacitive Current Compensation, Distribution Network, Petersen Coil, Single-Phase Earth Fault